Transformer K-Factor Harmonics Rating Calculator

Calculate Transformer K-Factor

Usually 100%.

Use our Transformer K-Factor Harmonics Rating Calculator to accurately determine the K-factor of your transformer based on harmonic current percentages. Essential for safely sizing transformers in environments with non-linear loads, protecting against overheating, and ensuring electrical system reliability. Calculate K-Factor quickly and efficiently for optimal transformer performance.

Formula:

The K-Factor (K) is calculated using the following formula:

K = ∑(Ih2 × h2) / ∑(Ih2)

Where:

  • Ih = The RMS current of the h-th harmonic, expressed as a percentage of the fundamental current (e.g., 100 for 100%, 20 for 20%).
  • h = The harmonic order (e.g., 1 for fundamental, 3 for 3rd harmonic, 5 for 5th harmonic).
  • The summations (∑) are carried out for all significant harmonic orders present in the load current.